Air Quality Testing and Monitoring

CI-v5 EQc5: Air Quality Testing and Monitoring 1-4 points

LEEDuser overview

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To support better management of IAQ and identify opportunities for health-based approaches to building operations. 

Requirements

Option 1. Pre-Occupancy Air Testing (1–2 points)
After construction ends and before occupancy, but under ventilation conditions typical for occupancy, conduct baseline IAQ testing. Retail projects may conduct the testing within 14 days of occupancy. The number of measurements should be specified according to Table 1 and taken in respective locations of the building.

Table 1. Number of Measurements Required for Preoccupancy Air Testing

Total Occupied Floor Area, sq. ft (sq. m.)

Number of Measurements

≤ 5,000 (500)

1

> 5,000 (500) and ≤ 15,000 (1,500)

2

> 15,000 (1,500) and ≤ 25,000 (2,500)

3

> 25,000 (2,500) and ≤ 200,000 (20,000)

4 plus one additional measurement per each 25,000 sq. ft. (2,500 sq. m.) above 25,000 sq. ft.

> 200,000 (20,000)

10 plus one additional measurement per each 50,000 sq. ft. (4,600 sq. m.) above 200,000 sq. ft.

 

PATH 1. PARTICULATE MATTER AND INORGANIC GASES (1 POINT) 
Test for the particulate matter (PM) and inorganic gases listed in Table 2, using an allowed test method, and demonstrate that the contaminants do not exceed the concentration limits listed in the table. Measure for a four-hour period and calculate the peak concentration for carbon monoxide and average concentration for ozone, PM2.5, and PM10.

Table 2. Limits for Particulate Matter and Inorganic Gases

Contaminant (CAS#)

Concentration Limit

(µg/m3)

Allowed Test Methods (laboratory-based)

Direct Reading Instrument Minimum Specifications

Carbon monoxide (CO)

9 ppm; no more than 2 ppm above outdoor levels

ISO 4224

EPA Compendium Method IP-3

GB/T 18883-2002 for projects in China

 

Direct calibrated electrochemical instrument with accuracy of ±3% of reading and resolution of 0.1 ppm 

 

NDIR CO sensors with accuracy of 1% of 10 ppm full scale and display resolution of less than 0.1 ppm

Particulates (for projects in attainment areas)

ISO class 8 or lower per ISO 14644-1:2015

 

OR meet

 

PM10: 50 μg/m3

 

PM2.5: 12 μg/m3

n/a

Accuracy (±): Greater of 5 μg/m3 or 20% of reading

Resolution (±): 5 μg/m3

IP-10A 

Particulates (for projects in nonattainment areas)

ISO class 8 or lower per ISO 14644-1:2015

 

OR meet

 

PM10: 50 μg/m3

 

PM2.5: 35 μg/m3

n/a

Accuracy (±): Greater of 5 μg/m3 or 20% of reading

Resolution (±): 5 μg/m3

IP-10A 

Ozone

0.07 ppm

 

OR 

 

0.01 ppm for projects pursuing EQc: Enhanced Air Quality, Option 1, Path 2

ISO 13964

ASTM D5149-02

EPA-designated methods for ozone

Monitoring device with accuracy greater of 5 ppb or 20% of reading and resolution (5 min average data) ±5 ppb

 

Note: ppm = parts per million; ppb = parts per billion.

AND/OR

PATH 2. VOLATILE ORGANIC COMPOUNDS (1 POINT)

  • Perform a screening test for total volatile organic compounds (TVOC). Use ISO 16000-6, EPA TO-17, or EPA TO-15 to collect and analyze the air sample. Calculate the TVOC value per EN 16516:2017; California Department of Public Health Standard Method v1.2 2017, Section 3.9.4; or an alternative calculation method, as long as the full method description is included in the test report. 
    • If the TVOC levels exceed 500 µg/m3, investigate for potential issues by comparing the individual VOC levels from the gas chromatography-mass spectrometry (GC/MS) results to associated cognizant authority health-based limits. Correct any identified issues and retest if necessary.
  • Test for the individual VOCs listed in Table 3 using an allowed test method and demonstrate that the contaminants do not exceed the concentration limits listed in the table. Laboratories that conduct the tests must be accredited under ISO/IEC 17025 for the test methods they use. 

Table 3. Volatile Organic Compound Limits

Contaminant (CAS#)

Concentration Limit

(µg/m3)

Allowed Test Methods

Formaldehyde 50-00-0

20 µg/m3 (16 ppb)

ISO 16000-3, 4; 

EPA TO-11a; 

EPA comp. IP-6A;

ASTM D5197-16

Acetaldehyde 75-07-0

140 µg/m3

Benzene 71-43-2

3 µg/m3

ISO 16000-6;

EPA IP-1;

EPA TO-17;

EPA TO-15;

ISO 16017-1, 2;

ASTM D6196-15

Hexane (n-) 110-54-3

7,000 µg/m3

Naphthalene 91-20-3

9 µg/m3

Phenol 108-95-2

200 µg/m3

Styrene 100-42-5

900 µg/m3

Tetrachloroethylene 127-18-4

35 µg/m3

Toluene 108-88-3

300 µg/m3

Vinyl acetate 108-05-4

200 µg/m3

Dichlorobenzene (1,4-) 106-46-7

800 µg/m3

Xylenes—total 108-38-3, 95-47-6, and 106-42-3

700 µg/m3

 

AND/OR 

Option 2. Continuous Indoor Air Monitoring (1 point)
Provide indoor air monitors for all of the following parameters:

  • Carbon dioxide (CO2)
  • Particulate matter (PM2.5)
  • TVOC
  • Temperature
  • Relative humidity

Monitors must be building grade or better and located between 3 and 6 feet (1–2 meters) above the floor. 
 

See all forum discussions about this credit »

Frequently asked questions

No results found
See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

For full access, sign up now for LEEDuser Premium

Already a premium member? Log in now

Checklists

Step by step to LEED certification

LEEDuser’s checklists walk you through the key action steps you need to earn a credit, including how to avoid common pitfalls and save money.

For full access, sign up now for LEEDuser Premium

Already a premium member? Log in now

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

For full access, sign up now for LEEDuser Premium

Already a premium member? Log in now


Addenda

This credit has no LEEDuser summary

See all forum discussions about this credit »

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To support better management of IAQ and identify opportunities for health-based approaches to building operations. 

Requirements

Option 1. Pre-Occupancy Air Testing (1–2 points)
After construction ends and before occupancy, but under ventilation conditions typical for occupancy, conduct baseline IAQ testing. Retail projects may conduct the testing within 14 days of occupancy. The number of measurements should be specified according to Table 1 and taken in respective locations of the building.

Table 1. Number of Measurements Required for Preoccupancy Air Testing

Total Occupied Floor Area, sq. ft (sq. m.)

Number of Measurements

≤ 5,000 (500)

1

> 5,000 (500) and ≤ 15,000 (1,500)

2

> 15,000 (1,500) and ≤ 25,000 (2,500)

3

> 25,000 (2,500) and ≤ 200,000 (20,000)

4 plus one additional measurement per each 25,000 sq. ft. (2,500 sq. m.) above 25,000 sq. ft.

> 200,000 (20,000)

10 plus one additional measurement per each 50,000 sq. ft. (4,600 sq. m.) above 200,000 sq. ft.

 

PATH 1. PARTICULATE MATTER AND INORGANIC GASES (1 POINT) 
Test for the particulate matter (PM) and inorganic gases listed in Table 2, using an allowed test method, and demonstrate that the contaminants do not exceed the concentration limits listed in the table. Measure for a four-hour period and calculate the peak concentration for carbon monoxide and average concentration for ozone, PM2.5, and PM10.

Table 2. Limits for Particulate Matter and Inorganic Gases

Contaminant (CAS#)

Concentration Limit

(µg/m3)

Allowed Test Methods (laboratory-based)

Direct Reading Instrument Minimum Specifications

Carbon monoxide (CO)

9 ppm; no more than 2 ppm above outdoor levels

ISO 4224

EPA Compendium Method IP-3

GB/T 18883-2002 for projects in China

 

Direct calibrated electrochemical instrument with accuracy of ±3% of reading and resolution of 0.1 ppm 

 

NDIR CO sensors with accuracy of 1% of 10 ppm full scale and display resolution of less than 0.1 ppm

Particulates (for projects in attainment areas)

ISO class 8 or lower per ISO 14644-1:2015

 

OR meet

 

PM10: 50 μg/m3

 

PM2.5: 12 μg/m3

n/a

Accuracy (±): Greater of 5 μg/m3 or 20% of reading

Resolution (±): 5 μg/m3

IP-10A 

Particulates (for projects in nonattainment areas)

ISO class 8 or lower per ISO 14644-1:2015

 

OR meet

 

PM10: 50 μg/m3

 

PM2.5: 35 μg/m3

n/a

Accuracy (±): Greater of 5 μg/m3 or 20% of reading

Resolution (±): 5 μg/m3

IP-10A 

Ozone

0.07 ppm

 

OR 

 

0.01 ppm for projects pursuing EQc: Enhanced Air Quality, Option 1, Path 2

ISO 13964

ASTM D5149-02

EPA-designated methods for ozone

Monitoring device with accuracy greater of 5 ppb or 20% of reading and resolution (5 min average data) ±5 ppb

 

Note: ppm = parts per million; ppb = parts per billion.

AND/OR

PATH 2. VOLATILE ORGANIC COMPOUNDS (1 POINT)

  • Perform a screening test for total volatile organic compounds (TVOC). Use ISO 16000-6, EPA TO-17, or EPA TO-15 to collect and analyze the air sample. Calculate the TVOC value per EN 16516:2017; California Department of Public Health Standard Method v1.2 2017, Section 3.9.4; or an alternative calculation method, as long as the full method description is included in the test report. 
    • If the TVOC levels exceed 500 µg/m3, investigate for potential issues by comparing the individual VOC levels from the gas chromatography-mass spectrometry (GC/MS) results to associated cognizant authority health-based limits. Correct any identified issues and retest if necessary.
  • Test for the individual VOCs listed in Table 3 using an allowed test method and demonstrate that the contaminants do not exceed the concentration limits listed in the table. Laboratories that conduct the tests must be accredited under ISO/IEC 17025 for the test methods they use. 

Table 3. Volatile Organic Compound Limits

Contaminant (CAS#)

Concentration Limit

(µg/m3)

Allowed Test Methods

Formaldehyde 50-00-0

20 µg/m3 (16 ppb)

ISO 16000-3, 4; 

EPA TO-11a; 

EPA comp. IP-6A;

ASTM D5197-16

Acetaldehyde 75-07-0

140 µg/m3

Benzene 71-43-2

3 µg/m3

ISO 16000-6;

EPA IP-1;

EPA TO-17;

EPA TO-15;

ISO 16017-1, 2;

ASTM D6196-15

Hexane (n-) 110-54-3

7,000 µg/m3

Naphthalene 91-20-3

9 µg/m3

Phenol 108-95-2

200 µg/m3

Styrene 100-42-5

900 µg/m3

Tetrachloroethylene 127-18-4

35 µg/m3

Toluene 108-88-3

300 µg/m3

Vinyl acetate 108-05-4

200 µg/m3

Dichlorobenzene (1,4-) 106-46-7

800 µg/m3

Xylenes—total 108-38-3, 95-47-6, and 106-42-3

700 µg/m3

 

AND/OR 

Option 2. Continuous Indoor Air Monitoring (1 point)
Provide indoor air monitors for all of the following parameters:

  • Carbon dioxide (CO2)
  • Particulate matter (PM2.5)
  • TVOC
  • Temperature
  • Relative humidity

Monitors must be building grade or better and located between 3 and 6 feet (1–2 meters) above the floor. 
 