Forum discussion

EBOM-2009 IEQp1:Minimum IAQ Performance

One outside air intake for multiple AHUs

Has anyone had experience documenting IEQp1 in the following situation?: I recently visited a facility that has one outdoor air intake for multiple AHUS. A single duct dumps outside air into a mechanical room on each floor. The mechanical rooms have 1-3 AHUS. The mechanical room acts as a mixing box that mixes outside air and return air. Based on the arrangement of units, I am confident that the air is fully mixed. Each air handling unit should receive a proportional amount of outside air. So in cases where there are 2 identical AHUS, each AHU should receive ½ of the outside air delivered into the mechanical room. I could potentially measure the airflow at the outside air supply and divide by 2, but I’m not sure how LEED reviewers would feel about it. The other alternative would be to add additional ductwork that directly ducts outside air to each AHU; however this seems to be an unnecessary expenditure. Has anyone had experience with this situation

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 03/06/2014 - 15:28

We've done a project similar to yours and , through a calculation as you described, we prorated the amounts of outside air to each AHU. The LEED reviewer approved this method. We were not required to duct the OA to each AHU. It may be wise to include a narrative/photo to help illustrate your method. Good Luck!

Add new comment

To post a comment, you need to register for a LEEDuser Basic membership (free) or login to your existing profile.